Yes, most sump and drainage pump control panels can add mobile SMS notifications while retaining the existing buzzer alarm.
More precisely, the alarm “sound” is not converted into a text message. Instead, an LTE/GSM remote alarm device receives the electrical alarm signal that activates the buzzer and sends an SMS.
Therefore, there is no need to replace the existing drainage pump and entire control panel. The key is to first check which alarm contacts the current control panel provides.
Condition |
Existing response |
How to add SMS notifications |
High water level in sump |
Buzzer and warning light activated |
Connect the high water level contact to the SMS device |
Pump overload |
EOCR relay activated |
Connect the fault output contact |
Pump stopped or tripped |
Control panel internal alarm |
Use the Fault contact |
Both 2 pumps faulty |
Common alarm activated |
Connect the Common Alarm contact |
Power outage |
Loss of power to the control panel |
Power outage detection and a communication device with a battery required |
Normal operation restored |
Alarm cleared |
Can be configured to send a restoration SMS as well |